Laboratory is supplied from 220 kV system using 230/120 kV/kV, 160 MVA autotransformer.
Laboratory's basic testing equipment consists of three short-circuit transformers with parameters per unit:
- short-circuit power 580 MVA / 5 s;
- primary voltage 115,5 kV;
- secondary voltage 1 - 32 kV step 1 kV.
Laboratory also performs tests of HV equipment with 123 kV supply voltage and current up to 2800 A.
Short-time withstand current and peak withstand current testsof Disconnectors and Earthing Switches according to IEC 62271-102 and IEC 62271-1